Manitowoc I0320 Specifiche Pagina 153

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 152
Part Number STH025 2/14 153
COLUMN 3 - TXV FLOODING OR REFRIGERANT
OVERCHARGE
A loose or improperly mounted expansion valve bulb
causes the expansion valve to flood. Check bulb
mounting, insulation, etc., before changing the valve.
Verify refrigerant amount is correct by weighing
recovered refrigerant before replacing a TXV.
COLUMN 4 - COMPRESSOR
Replace the compressor. To receive warranty credit,
the compressor ports must be properly sealed by
crimping and soldering them closed.
Vedere la pagina 152
1 2 ... 148 149 150 151 152 153 154 155 156 157 158 ... 271 272

Commenti su questo manuale

Nessun commento