Manitowoc S model Specifiche Pagina 164

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 163
164 Part Number 80-1230-9 10/10
Water Level Probe Closed or Shorted
1. Disconnect the water level probe from the control
board.
2. Move the toggle switch to the ICE position, wait
45 seconds and then monitor the Water Level
Probe light.
Step 2 Disconnect water level probe from control board
“water level” terminal
Water Level
light is:
Compressor Cause
Off Remains
de-energized
Clean water
level probe.
On Energizes Replace control board.
DISCONNECT
WATER LEVEL PROBE.
WATER LEVEL
PROBE LIGHT
Vedere la pagina 163
1 2 ... 159 160 161 162 163 164 165 166 167 168 169 ... 291 292

Commenti su questo manuale

Nessun commento