110 Part Number STH042 3/14
4. Recovered refrigerant must come from a
“contaminant-free” system. To decide whether the
system is contaminant free, consider:
Type(s) of previous failure(s)
Whether the system was cleaned, evacuated
and recharged properly following failure(s)
Whether the system has been contaminated
by this failure
Compressor motor burnouts and improper past
service prevent refrigerant re-use.
Refer to “System Contamination Cleanup” on
page 114 to test for contamination.
5. “Substitute” or “Alternative” Refrigerant
Must use only Manitowoc-approved alternative
refrigerants.
Must follow Manitowoc-published conversion
procedures.