Part Number STH042 3/14 79
Suction Pressure High Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
on page 64.
Discharge Pressure
Discharge pressure is too high, and is affecting
suction pressure, refer to
“Discharge Pressure
High Checklist” on page 76.
Improper Refrigerant Charge
Overcharged
Wrong type of refrigerant
Non-condensable in system
Other
Non-Manitowoc components in system
Harvest valve leaking
TXV flooding (check bulb mounting)
Defective compressor